PV-02

Producing

PV array · Meyer Burger Glass 390 bifacial · Muttsee

ModulesUnderperforming2
Effective irradiance, W/m²0425850
Producing
Live
Now
Polled every 5 seconds; the 3D model follows these values.
56% of rated

Tilt / azimuth

68° / 166°

Front irradiance

499 W/m²

Rear irradiance

122 W/m²

Bifacial gain

+18.4 %

Snow on modules

3 %

Lost to snow

192 kWh

Last slide-off

09:33

Rated power

370 kWp

Output now

207.5 kW

Energy today

1,552 kWh

Lifetime

2,629 MWh

Availability

96.01 %

Runtime

3,884 h

Next service

in 746 h

Last seen

13:59:45

Modules
Module health
Every module reports on its own. Hover one in the 3D view for its reading; faults blink red, underperforming modules blink amber.

Total

60

Normal

58

Underperforming

2

Fault

0

Snow covered

0

Needing attention

R1-05B

Soiling from rockfall dust

Table 1 · column 5 · upper row

82 % of expected

Underperforming

R2-02B

Cracked cells

Table 2 · column 2 · upper row

68 % of expected

Underperforming

Telemetry

Front irradiance

499.00 W/m²

Rear irradiance

122.00 W/m²

Module temperature

8.20 °C

Snow on modules

3.00 %

Wind gust

10.60 m/s

Snow load

3.47 kN/m²

String voltage

1,207.00 V

String current

7.51 A

Ambient

-4.30 °C

History
Power and snow-free potential
Active power against what the asset would make with clean modules. The gap is the snow loss.
Today
Hourly energy
MWh delivered and lost to snow, hour by hour since midnight.
Alarms
Asset alarms
Open and recent events for this asset.

String current imbalance

PV-02· 11-18 01:46
Low