PV-04

Producing

PV array · Meyer Burger Glass 390 bifacial · Gondo

ModulesFault2Underperforming3
Effective irradiance, W/m²0425850
Producing
Live
Now
Polled every 5 seconds; the 3D model follows these values.
64% of rated

Tilt / azimuth

90° / 177°

Front irradiance

659 W/m²

Rear irradiance

105 W/m²

Bifacial gain

+12.0 %

Snow on modules

3 %

Lost to snow

158 kWh

Last slide-off

07:41

Rated power

1,250 kWp

Output now

803.0 kW

Energy today

5,754 kWh

Lifetime

3,444 MWh

Availability

98.14 %

Runtime

1,016 h

Next service

in 566 h

Last seen

13:59:51

Modules
Module health
Every module reports on its own. Hover one in the 3D view for its reading; faults blink red, underperforming modules blink amber.

Total

176

Normal

171

Underperforming

3

Fault

2

Snow covered

0

Needing attention

T01-A1-4

Potential-induced degradation

Tree 1 · wall A · wing 1 · row 4

78 % of expected

Underperforming

T03-B1-4

Bypass diode shorted

Tree 3 · wall B · wing 1 · row 4

68 % of expected

Underperforming

T04-A1-2

Junction box failure

Tree 4 · wall A · wing 1 · row 2

Fault

T09-B1-4

Broken glass after hail

Tree 9 · wall B · wing 1 · row 4

Fault

T10-B1-2

Bypass diode shorted

Tree 10 · wall B · wing 1 · row 2

64 % of expected

Underperforming

Telemetry

Front irradiance

659.00 W/m²

Rear irradiance

105.00 W/m²

Module temperature

18.70 °C

Snow on modules

3.00 %

Wind gust

6.40 m/s

Snow load

1.24 kN/m²

String voltage

1,207.00 V

String current

8.67 A

Ambient

2.30 °C

History
Power and snow-free potential
Active power against what the asset would make with clean modules. The gap is the snow loss.
Today
Hourly energy
MWh delivered and lost to snow, hour by hour since midnight.
Alarms
Asset alarms
Open and recent events for this asset.

No alarms on this asset.