Saflisch

Needs attention

Valais · 2,440 m · Freestanding bifacial, tilt 60° / 65° · 13.80 MWp · manager Marco Bundi

Snow monitoring
Output now

6.78 MW

Energy today

57.0 MWh

Lost to snow

8.0 MWh

Snow on modules

3 %

Bifacial gain

+15.6 %

Open alarms

4

Generation
Since sunrise
Front and rear side of the bifacial modules, the power snow on the modules cost, and the battery (charging shows below zero).
Conditions
Snow, weather and grid

Snow depth

74 cm

Fresh snow 24 h

9 cm

Albedo

0.78

Snow load

2.2 / 5.4 kN/m²

Irradiance (GHI)

240 W/m²

Sun elevation

15.3°, azimuth 217°

Temperature

-0.6 °C

Wind

5.3 m/s ESE, gusts 9

Cloud cover

7 %

Substation

Ernen 65 kV

Voltage

65.1 kV

Frequency

50.016 Hz

Curtailment

6 %

Spot price

174.22 CHF/MWh

Assets

17 assets on this plant. Open one for its live 3D view.

PV array

PV-01

Jinko Tiger Neo bifacial · 1,100 kWp

Producing
65%

Output

720 kW

Today

4,835 kWh

Snow on modules

3 %

PV array

PV-02

Jinko Tiger Neo bifacial · 1,200 kWp

Producing
61%

Output

730 kW

Today

5,342 kWh

Snow on modules

3 %

PV array

PV-03

Meyer Burger Glass 390 bifacial · 1,100 kWp

Producing
65%

Output

716 kW

Today

5,154 kWh

Snow on modules

3 %

PV array

PV-04

Jinko Tiger Neo bifacial · 1,100 kWp

Fault
0%

Output

0 kW

Today

0 kWh

Snow on modules

3 %

PV array

PV-05

LONGi Hi-MO 6 bifacial · 1,100 kWp

Producing
68%

Output

750 kW

Today

4,818 kWh

Snow on modules

3 %

PV array

PV-06

LONGi Hi-MO 6 bifacial · 1,100 kWp

Producing
63%

Output

692 kW

Today

4,839 kWh

Snow on modules

3 %

PV array

PV-07

Jinko Tiger Neo bifacial · 1,200 kWp

Producing
63%

Output

751 kW

Today

5,506 kWh

Snow on modules

3 %

PV array

PV-08

Jinko Tiger Neo bifacial · 1,200 kWp

Producing
62%

Output

745 kW

Today

5,474 kWh

Snow on modules

3 %

PV array

PV-09

Jinko Tiger Neo bifacial · 1,200 kWp

Producing
61%

Output

729 kW

Today

5,234 kWh

Snow on modules

3 %

PV array

PV-10

LONGi Hi-MO 6 bifacial · 1,200 kWp

Producing
64%

Output

767 kW

Today

5,507 kWh

Snow on modules

3 %

PV array

PV-11

LONGi Hi-MO 6 bifacial · 1,100 kWp

Producing
65%

Output

719 kW

Today

4,842 kWh

Snow on modules

3 %

PV array

PV-12

Jinko Tiger Neo bifacial · 1,200 kWp

Producing
64%

Output

769 kW

Today

5,468 kWh

Snow on modules

3 %

Inverter station

INV-01

SMA Sunny Central 2750-EV · 3,280 kVA

Producing
60%

Output

1,968 kW

Today

13,872 kWh

Availability

99.8 %

Inverter station

INV-02

Sungrow SG350HX · 3,280 kVA

Producing
60%

Output

1,979 kW

Today

13,952 kWh

Availability

99.7 %

Inverter station

INV-03

Huawei SUN2000-330KTL · 3,280 kVA

Curtailed
33%

Output

1,094 kW

Today

7,711 kWh

Availability

99.9 %

Inverter station

INV-04

SMA Sunny Central 2750-EV · 3,280 kVA

Producing
61%

Output

1,996 kW

Today

14,070 kWh

Availability

98.2 %

Battery

BESS-01

Fluence Gridstack Pro · 2,500 kW

Producing
52%

Output

1,308 kW

Today

0 kWh

State of charge

85 %

Alarms
Plant alarms
Most recent events from this plant's assets.

Enclosure heating active

BESS-01· 11-18 06:42
Low

Export limited by grid operator setpoint

INV-03· 11-18 06:09
Medium

String fuse blown, 4 strings offline

PV-04· 11-18 02:39
High

Rear-side irradiance sensor iced

PV-04· 11-18 02:27
High