PV-06

Producing

PV array · Meyer Burger Glass 390 bifacial · Gondo

ModulesFault1Underperforming5
Effective irradiance, W/m²0425850
Producing
Live
Now
Polled every 5 seconds; the 3D model follows these values.
68% of rated

Tilt / azimuth

90° / 180°

Front irradiance

682 W/m²

Rear irradiance

105 W/m²

Bifacial gain

+11.6 %

Snow on modules

3 %

Lost to snow

183 kWh

Last slide-off

08:02

Rated power

1,400 kWp

Output now

951.6 kW

Energy today

6,595 kWh

Lifetime

3,857 MWh

Availability

98.92 %

Runtime

1,162 h

Next service

in 1,041 h

Last seen

13:59:55

Modules
Module health
Every module reports on its own. Hover one in the 3D view for its reading; faults blink red, underperforming modules blink amber.

Total

176

Normal

170

Underperforming

5

Fault

1

Snow covered

0

Needing attention

T06-A1-3

Bypass diode shorted

Tree 6 · wall A · wing 1 · row 3

70 % of expected

Underperforming

T06-B2-1

Shaded by a snow cornice

Tree 6 · wall B · wing 2 · row 1

47 % of expected

Underperforming

T08-B1-4

Open DC connector

Tree 8 · wall B · wing 1 · row 4

Fault

T10-A1-2

Shaded by a snow cornice

Tree 10 · wall A · wing 1 · row 2

49 % of expected

Underperforming

T10-A2-4

Soiling from rockfall dust

Tree 10 · wall A · wing 2 · row 4

89 % of expected

Underperforming

T11-B1-4

Hot spot on the front glass

Tree 11 · wall B · wing 1 · row 4

77 % of expected

Underperforming

Telemetry

Front irradiance

682.00 W/m²

Rear irradiance

105.00 W/m²

Module temperature

19.30 °C

Snow on modules

3.00 %

Wind gust

6.40 m/s

Snow load

1.24 kN/m²

String voltage

1,195.00 V

String current

9.05 A

Ambient

2.30 °C

History
Power and snow-free potential
Active power against what the asset would make with clean modules. The gap is the snow loss.
Today
Hourly energy
MWh delivered and lost to snow, hour by hour since midnight.
Alarms
Asset alarms
Open and recent events for this asset.

No alarms on this asset.